LXC7110 generator controller
- publish: 2019-08-03 16:58 Browse:
- Type: LXC7110
- Product Summary:
Description Control function automatically switches mains power monitoring and mains/power generation added to the LXC7110 based on(AMF),especially suitable for stand-alone automated systems.Its mainfeatures are as follows: *32-bit ARM mircrocontroller,hardware integration and high reliablity have been further enhanced. *The oversized LCD LCD240*128,with backlight,Chinese,English and other languages optional interface operation.All parameters can ...
Description
Control function automatically switches mains power monitoring and mains/power generation added to the LXC7110 based on(AMF),especially suitable for stand-alone automated systems.Its main features are as follows:
*32-bit ARM mircrocontroller,hardware integration and high reliablity have been further enhanced.
*The oversized LCD LCD240*128,with backlight,Chinese,English and other languages optional interface operation.All parameters can be set on the controller,convenient debugging personnel test machine.
*Of Things Internet through GPRS mobile network and the Internet,in any network can remote monitoring.
*Particularly for the management of the leasing industry provide the perfect solution:remote management via PC leased units Monitor all operating parameters(oil pressure,water temperature,voltage,current,power,etc.)can change the configuration at any time to protect inappropriate application of the unit,recorded 200 detailed fault information,including:time to failure,because,when the key parameters of voltage,current,power,oil pressure,water temperature,etc,and etc.,and at any time can be uploaded to the monitoring machine.Another multi-level password management items to facilitate the lease management.
*RS485 communication interface, using the MODBUS protocol can achieve "three remote" function.
*Control and protection functions: diesel or natural gas generator sets, automatic start / stop, sub-gate (ATS switch)Perfect failure protection.
Working voltage | 8.0-35Vdc continuous |
Alternator votage input:Three-phrase four wire | 20V AC-360VA(ph-N)3 Phase 4 wire |
Three-phrase three wire | 30V AC-620V AC(ph-ph)3 Phase 3 wire |
Single-phrase two wire | 20V AC-360V AC(ph-N) |
Two-phrase three wire | 20V AC-360V AC(ph-N) |
Overall Power Consumption | <3W(Standby mode:<=2W) |
AC generator frequence | 50/60HZ |
Speed Sensor voltage Vpp | 1.0-70V(Peak to Peak) |
Speed Sensor frequence | 10,000 Hz (max) |
Starting relay output | The 16Amp controller power supply voltage output |
Fuel relay output | The 16Amp controller power supply voltage output |
Programmable relay outputs 1 | 7Amp 250VAC passive output |
Programmable relay outputs 2 | 7Amp 250VAC passive output |
Programmable relay outputs 3 | 16Amp 250VAC passive output |
Programmable relay outputs 4 | 16Amp 250VAC passive output |
Programmable relay outputs 5 | The 7Amp controller power supply voltage output(LXC7220) |
Programmable relay outputs 6 | The 7Amp controller power supply voltage output(LXC7220) |
Body Size | 210mm*152mm*48nn |
The size of holes | 186mm*141mm |
Current transformer secondary current | Specified 5A |
Working condition | Temperature:(-25-+70degrees)humidity:(20-90)% |
Storage Conditions | Temperature:(-40-+80degrees) |
Protection class | IP55:when the installation of waterpoof rubber ring between the controller and the control panel. |
IP42:when the installation of waterpoof rubber ring between the controller and the control panel does not. | |
Dielectric Strength | Object:Between the input/output/power |
Reference standard:IEC688-1992 | |
Test Methods:AC1.5kV/1min Leakage current:3mA | |
Weight | 0.68kg |