Your postion: > Dynamic news > Industry news >

Generating set how the cloud controller remote monitoring unit

2016-10-20 14:58      Click:

Generating set how the cloud controller remote monitoring unit

How the cloud controller remote monitoring of generator set

Industrial iot cloud controller can be perfect for you to solve the user of the era of these problems, it USES the advanced WIFI connection patent technology, not achieve mobile phone CARDS, regardless of national borders open network, as long as have a smartphone, can make generating set and connection of cloud services platform.
This is the era of Internet of things cloud controller

 

Cloud controller remote fault diagnosis technology, can quickly diagnose the cause of the problem, and provide emergency and long-lasting solutions, resulting in the timely solve the problems.

Case diagnosis

LIXISE health cloud by force, the length of the cause of the problem in a diagnosis of over-current protection

When generating set in over-current protection down, need to be aware of the various data of the fault protection moment, in the past, this is impossible, because failure has happened already downtime, how through? LIXISE black box technology allows you to accurately show every second:

From the chart of 17 points, we can see:

★ Power line voltage= 393.4VAC

The excitation voltage= 34.4VDC 

Load currentL1 = 183.7A

Load currentL1 = 182.1A

Load currentL1 = 170.2A

Load power= 122.2KW

From the chart can be analyzed out: after increasing load, the load current started to rise, the power of 122.2 KW, and the power rating of the unit is 100 KW, more than 22.2 KW, and duration of 9 seconds, thus cause the over-current protection action of the controller.In addition, can see from the curve is not caused by short circuit protection, and so can suggest the customer should pay attention to in the future, do not overload use.

To diagnose the fault cause of the failure of the starting unit

When generating set starting failure, need to remote check the various data in the process of starting, to determine the cause of the problem, in the past, this is impossible, because no way to check through back to the starting process, must be experienced technical personnel to the scene using a multimeter, and repeatedly starting measurement to get the data:

Control the fuel output voltage is normal?

What is the speed of the boot process?

Does the battery without electricity in the process of start?

How much is the oil pressure in the boot process?

In the process of start generator frequency is how much?

Programmable input port state in the process of start?

Programmable input port state in the process of start?

Now you can LIXISE cat black box technique of cloud, collected fault happens every seconds instant data, and pass through the way of chart display as follows, for you to understand the changing process of related parameters:

★ Rotate speed= 275.8 RPM

The battery voltage = 17.3 V

Before starting the battery voltage = 25.2 V

★ Electronic governor voltage= = 0 V

The fuel output = 1 (logic 1 output)

Starting output = 1 (logic 1 output)

Oil pressure = 356

Generator frequency = 0 (starting generator haven't send out electricity)

Can be analyzed from the figure out: during the period of starting, the controller of normal fuel output speed also has 270-290 revolutions, oil pressure and at normal pressure, but why should start failure?Look at the output of the electronic governor, found that 0 v, show that no output voltage to open the fuel, eventually leading to failure starting.

Generator the advantage of the cloud controller

Using three different WIFI connection, unlimited Internet presence, unlimited geographic borders, any places and conditions can achieve data transmission.

The first kind of connection mode: in the application environment itself with wi-fi networks, cloud controller directly connected to the WIFI network, WIFI network between generator and cloud servers to establish real-time communication pipeline, real-time remote monitoring and control.

The second mode of connection: no WIFI in the application environment, but has a mobile phone networks, via mobile phone share the WIFI, also realize real-time remote monitoring, but usually for more for health inspection and remote fault diagnosis

The third kind of mode of connection: no WIFI in the application environment, no mobile phones network, through the APP to save the cloud controller of 7 kinds of data (can run 24 hours to save half a year) to save to the handset, until the phone to have WIFI or Internet environment, and will save the data to the cloud server, realize the remote fault diagnosis and fault early warning, early health check

First introduced the global cloud controller, in terms of cloud services, research and development strength more than foreign brands

The black patent technology

Principle: there is a small cache in our controller, designed to cache the latest data from tens of seconds, to monitor when a failure occurs, immediately will cache the data saved to the internal mass storage, at the same time also packaged these data to the cloud server, realize the black box recording function.When we use cell phones or PC terminal access these data to the server, you can like to play video reproduce all the data before failure for a period of time

 

Eight advantage generators cloud controller

Monitoring and recording equipment running status anytime and anywhere

Monitoring and data analysis, troubleshooting problems in advance

When a failure occurs, alarm notice in a timely manner

Reproduce the failure site (black) provide the basis for maintenance

Provide service reminders, extend equipment life

Automatically generate reports, tube historical data

Steady and fast, and never drop of communication

Provide the bidding management, sharing resources

 


Dongguan Tuancheng automation equipment Co., Ltd. all rights reserved.
Sales Phone: 86-769-23162896 Fax:86-769-23162896-609、23166296