LIXISE generator governor performance metrics
The performance of the diesel engine generator governor directly affects the
stability and reliability of the operation. Generator governor installed in the
diesel engine, performance appraisal, deal with the diesel engine the mutation
load test, at the same time with the rotational speed automatic recorder to
record the engine speed variation curves, used for performance analysis of
generator governor. Control process of speed change curve shown in figure 2-87
curve of a diesel engine is obtained when the mutation load test. Diesel
machines stable running at the highest speed no max, in a transient process with
full load, speed immediately dropped, instantaneous speed dropped to the lowest
instantaneous speed nmin. Then the generator speed governor, again, after a
period of time Ts and by several convergence movements, stable speed at full
load steady speed nb. This adjustment process called transition process control.
The test can also from behind a dump full load start, speed suddenly increased
to the highest instantaneous speed of nmax, the governor control, speed down
again, after TS time, speed and stability at high idling speed
nomax.
Figure 2-87 speed adjustment process of speed change curve
Accordingly, the
generator speed governor performance evaluation has the following two kinds of
work index.
(1) dynamic index
Dynamic index is used to evaluate
performance of the transition process control system (stability), see figure
2-87.
1) the instantaneous timing rate δ 1
Unload all load
instantaneous adjustable rate δ 1+ =nmax - NB /nb X100% (2 - 16)
The
sudden load instantaneous adjustable rate δ 1- =|nmin - nomax /nb | X100% (2 -
17)
Chinese related standard diesel engine δ 1+ δ ≤ 10%; 1- (process plus
50% plus 50% of full load) ≤ 10%.
2) stability time Ts
Stable time
-- from a sudden (or sudden) fluctuation range of full load speed just deviates
from the maximum no-load speed (or calibration speed fluctuation range)
fluctuation range to speed recovery to the calibration speed (fluctuation range
or highest no-load speed) until the time required (s). The provisions China
relevant norms, alternator TS ≤ 5S.
(2) static index
1) stable
rate δ 2
Stable rate when the control handle in the calibration of oil
position, maximum no-load speed of nomax and the rated speed nb. The difference
between the rated speed nb. The percentage of the ratio, the δ
2=nomax-nb/nbx100% (2 - 18)
Stable rate δ 2 is used to measure the
accuracy of the governor, the smaller the value, the accuracy of the governor
said. Delta 2 abroad called speed (speed drop). The single diesel engine
operation allows the δ 2 = 0, the engine would not vary with changes in external
load while maintaining constant speed operation. But diesel engine work in
parallel in a few stations, in order to make the machine load distribution is
reasonable, the machine must be accounted for: equal and shall not be zero.
Requirements for the delta 2 should be based on the use of diesel engine set.
The provisions Chinese relevant norms, marine δ 2<10% δ 2<5% host; AC
generator.
2) speed fluctuation rate phi. Or the speed change rate of
PSI
Variation was used to characterize the diesel in the stable operation
speed of the machine, is mainly composed of a diesel engine torque caused by
uneven. But the two different definitions. Speed fluctuation rate
With
=|ncmax (ncmin) -nm/nm|x100% (2 - 19)
Speed variation ratio
A
ncmin/nm ψ =ncmax x100% (2 - 20)
The highest speed of ncmax during the
determination, r/min;
Ncmin determination of minimum speed period,
r/min;
Nm determination of average speed, during the r/min, NM = (ncmax +
ncmin) /2.
In general, in the calibration mode diameter ≤ (0.25 - 0.5)%;
psi (0.5 ≤ 1)%.
3) not sensitivity epsilon.
When the diesel engine
under a certain load under stable operation, due to the clearance, friction and
resistance speed regulating mechanism, if the speed is changed slightly, the
governor can not immediately change the fuel supply quantity, until the speed
variation is large enough the governor can begin to adjust supply function. This
phenomenon is called the governor's insensitivity. Domestic less sensitivity
represents insensitive area size.
Let e = n2- n1/ nm x 100% (2 -
21)
Type in. Speed n1 diesel is reduced, the governor begins speed,
r/min;
N2 diesel engine speed increases, the governor begins speed,
r/min;
The average speed of nm diesel engine, r/min, NM = (n1+n2)
/2.
No sensitivity will cause the engine speed is not stable, will lead
to serious loss of effect of speed governor, general provisions at rated speed e
≤ 1.5% 2%; while in the lowest stable speed - ≤ 10%-13%.
LIXISE force ksetra-ksetrajnaEG2000 generator governor
Governor product performance and
characteristics of EG2000:
The use of 1 broad frequency range
2
15Amp high current output
3 suitable all kinds of steam, diesel and
natural gas engines
4 high sensitivity, speed change
5 resin
infusion, moisture-proof, seismic, antioxidant, high reliability
6 can be
connected with the remote speed controller or remote speed control
potentiometer
7 engine idle speed setting function and control terminal
for remote use