LIXISE sharing small generators in parallel controller techn
Talked about small generators in
parallel controllers, we need to understand "what is a small generator?" Usually
refers to power less than 30kw can be called small generators. Similarly in small generators can
be achieved and the network controller, said the small generators in parallel
controllers. We
are committed to developing LIXISE people have been studies in this area.
Here we share with you the simple
to achieve small generators in parallel technology.
Small hydro fuel generators or
condition group and power grid are: three-phase AC generator set output voltage,
frequency, phase sequence must be the same as the grid. This article describes the small
generators and network controller, to set the output voltage of the generator
automatic detection and control, auto-complete when they meet and network
conditions and net work.
It should be noted: The small
generators and power grid, subject to approval and testing electrical control
department before implementation qualified.
Circuit works
The small generators and network
controller circuit by the sampling circuit, comparator circuit, delay control
circuit and working status indication circuit shown in Figure 1.
Sampling circuit consists of
resistors Rl-R3, R9-Rll, potentiometer RPl, RP3, rectifier diode VD7-VDlO,
VDl5-VDl8 and capacitors Cl, C3 components.
The comparator circuit consists
of an operational amplifier integrated circuit IC (Nl, N2), a diode VDl-VD4,
VDll-VDl4, resistors R4, R5, Rl2 and R13 components.
Delay control circuit consists of
resistors R6, potentiometer RP2, diode VD4-VD6, VDl4, capacitor C2, transistor
Vl, relay K and AC contactor KM components.
Work status indication circuit
consists of a light emitting diode VLl, VL2, V2 transistors and resistors R7, R8
components.
After the step-down voltage by Rl
grid generators L2 L2 phase and the phase between the lines, VD7-VDlO
rectification, R2 and R3, RPl partial pressure and Cl filtering, as applied to
the sampling voltage through R4 lC 2 feet, and 3 pin 0.6V reference voltage.
When the voltage of the IC 2 feet
higher than 0.6V, 1 pin output low, C2 by VD5, VD4 for IC 2 feet quickly
discharge, the VD4 deadline, + l2V voltage through R6, Rn charge on C2, the
delay period After time, Vl conduction, K and
KM pull, KM normally open contacts connected, complete and net-work; while also
conducting V2, VLl lit, and the network issued instructions.
Sampling and comparison process
between the control grid voltage of phase L3 L3 phase with the generator
described above.
If the sampling voltage on Cl or
C3 zero over a very short duration, then the grid conditions are not met, C2
immediately after charging a small amount of electrical discharge, Vl is not
turned on, and the network can not be achieved.
K R rejection makes adjusting the
delay 0.5-1s after the action.
Components Selection
RI and Rg are selected 1/2W metal
film resistors; full-R8 and RlO-R13 1/4W metal film resistor or a carbon film
resistors.
RPl-R are made of organic solid
variable resistor.
Cl-C3 are selected voltage is 16V
aluminum electrolytic capacitors.
VDl-VDl8 1N4007 type silicon
rectifier diodes.
VLl and V are selected p5mm
ashamed of light-emitting diodes, VLl choose red, V ashamed choose green.
Vl use S805O or C8050, 3DG8050
silicon NPN transistor; V2 selection 3CG2l or Sg015 silicon PNP transistor.
IC op amp selection C250.
K selection l2V DC relay.
KM and knife switch
Q1, Q2 should be based on the
power of the load may be.
Summary: LIXISE intelligent
control of the generator has been committed to research and development,
especially in the generator parallel studies continue to increase investment in
technology, research and development is now ready to small generators in
parallel controllers and other ancillary products. To meet a variety of customer
needs. With your support, we will
redouble our efforts!