EVR106 (AVR) is a generator automatic voltage regulator based on half-wave phase-controlled rectifier excitation principle. The device that stabilizes the output voltage of the alternator by adjusting the excitation current of the generator. Used as auxiliary windings, phase power supply as the excitation power generator. With high stability, fast response, easy installation and maintenance features. 1, S1, S2 for the current compensation input, a...
EVR106 (AVR) is a generator automatic voltage regulator based on half-wave phase-controlled rectifier excitation principle. The device that stabilizes the output voltage of the alternator by adjusting the excitation current of the generator. Used as auxiliary windings, phase power supply as the excitation power generator. With high stability, fast response, easy installation and maintenance features.
1, S1, S2 for the current compensation input, and the machine, the access ratio is In / 5A, the capacity of 5VA adjustable current transformer (CT) output.
2, A1, A2 for the analog voltage regulator input, can be connected to an external ± 5Vdc adjustable voltage source.
3, if the need for remote voltage adjustment, can be in VR1, VR2 can be connected between a 10 ~ 100KΩ / 1 ~ 2W potentiometer, otherwise, must be shorted!
* Adjustable soft start circuitry is included to provide a smooth controlled build up of generator output voltage.
Sensing Input | Voltage | 180~250Vac | |
Frequency | 50-60 Hz nominal | ||
Power Input | Voltage | 180~300 Vac | |
Current | 5A | ||
Frequency | 50/60 HZ | ||
Output | Voltage | Max 180V dc | |
Current | Continuous5 A, Intermittent 6A for 10 secs | ||
Resistance | 10 KΩ-100KΩ | ||
Regulation | +/- 0.5% RMS with 4% engine governing | ||
Thermal Drift | 0.02% per Deg. C change in AVR ambient | ||
Soft Staret Ramp Time | 0.4 - 4 seconds | ||
Typical system response | AVR response | 20ms | |
Filed current to 90% | 80 ms | ||
Machine Volts to 97% | 300ms | ||
External voltage adjustment | +/-10% with 5k ohm 1 watt trimmer | ||
Under frequency protection | Set point | 95% Hz | |
Slope | 100%-300% down to 30 Hz | ||
Max. Dwell | 20% volts/S recovery | ||
Unit power dissipation | 18 watts maximum | ||
Analogue Input | Maximum input | +/- 5 Vdc | |
Sensitivity | 1v for 5% Generator Volts (adjustable) | ||
Input resistance | 1k ohm | ||
Quadrature Droop Input | 10 ohms burden | ||
Max. sensitivity: 0.22 A for 5% droop 0PF | |||
Max. input: 0.33A | |||
Environmental | Vibration | 20-100 Hz,50mm/se | |
100Hz – 2kHz, 3.3g | |||
Operating temperature | -40 to +70 Deg. C | ||
Relative Humidity 0-70 Deg. C | 95% | ||
Storage temperature | -55 to +80 Deg. C |