EAM100 Electronic governor
- publish: 2014-03-16 07:00 Browse:
- Type: EAM100
- Product Summary:
The EAM100 is an electronic device that allows GAC Load Sharing Modules and Auto Synchronizers to operate with the Cummins EFC electronic speed controls P/N is 3098693, 3062323, 3044196,3044195, 3037359 and 3032733. Sophisticated generator paralleling systems can assembled with GAC high performance accessories control EFC equipped Cummins engines....
Product description
The EAM100 is an electronic device that allows GAC Load Sharing Modules and Auto Synchronizers to operate with the Cummins EFC electronic speed controls P/N is 3098693, 3062323, 3044196,3044195, 3037359 and 3032733.
Sophisticated generator paralleling systems can assembled with GAC high performance accessories control EFC equipped Cummins engines.
The EAM100 module requires four connections to the EFC speed control. The positive lead from the battery supply,signal ground from Terminal 11 (not battery ground). the reference sensing,and an output to the speed control to adjust its speed setting. The EAM100 draws less than one microamp from the speed control, assuring no adverse effects on the system.
The other terminal block on the EAM100 accepts connections from an external speed trim pot, GAC P/N TP501 or TP503,and from the GAC Load Sharing Module and Auto Synchronizer.
Main features:
1、GAC load distribution module allows automatic synchronization and simultaneously work;
2、EAM100 the current drawn from the speed controller to not more than 1mA, to ensure no adverse impact on the system;
3、Compatible GAC governor;
Specifications
Input impedance (Terminals D&A): 60K ohms
Output impedance (Terminals 11&12): 5.8K Ohms
Nominal output voltage (Terminals 11&12): 1.50V DC
Output voltage range (Terminals 11&12): 0-2.6V DC
Nominal input voltage (Terminals D&A): 5.OV DC
Transfer function: -1.9 volts/ volt(without trim pot)
-1.1 volts/ volt (with trim pot)
Temperature range: -40℃ to +85℃
DC supply range (Terminals 1&12):15 to 32V DC
DC supply current (Terminals 1&12): 20 mA
Trim Pot (Terminals A, B,&C): use 5K trim potentiometer