AVC63-12B1 Generator AVR
- publish: 2019-07-26 15:41 Browse:
- Type: AVC63-12B1
- Product Summary:
Description: The AVC63-12B1 Voltage Regulator is contained in an encapsulated plastic case. sensing: 220VAC ,output: 12A/65V.For 50 or 60 Hz brushless generators.The regulator includes frequency compensation with selectable slope, inverse time over-excitation shutdown, solid-state build-up circuitry, single-phase or three-phase voltage sensing, single-phase or three phase shunt, or permanent magnet power input, and parallel droop compensation, and...
Description:
The AVC63-12B1 Voltage Regulator is contained in an encapsulated plastic case. sensing: 220VAC ,output: 12A/65V.For 50 or 60 Hz brushless generators.The regulator includes frequency compensation with selectable slope, inverse time over-excitation shutdown, solid-state build-up circuitry, single-phase or three-phase voltage sensing, single-phase or three phase shunt, or permanent magnet power input, and parallel droop compensation, and an accessory input. The accessory input provides compatibility (分行点)with accessories such as a var/power factor controller.
VR6 | ||
Specification | K65-12B | K125-10B |
Output power(with a 240 Vac input) | 12Adc @ 65 Vdc Max cfontainuous; 25 Adc @ 125 Vdc forcing for 10 seconds | 10 Adc @ 125 Vdc max continuous. 20 Adc @ 250 Vdc forcing for 10 seconds. |
AC input power | 100 to 280 Vac, single-phase 50 to 400 Hz; or 63 to 105 Vac three-phase, 50 to 400 Hz; 1092 VA max continuous burden | 180 to 280 Vac, single-phase or three-phase, 50 to 400 Hz, 1750 VA max continous burden. |
AC sensing voltage | 90 to 140 Vac, 50/60 Hz; single-or-three phase. | 90 to 140 Vac, 50/60 Hz; single-or-three phase. |
External voltage adjust rheostat | 10K ohm, 2W, potentiometer | 10K ohm, 2W, potentiometer |
Regulation accuracy | ±0.5% Average responding | ±0.5% Average responding |
Voltage drift | ±1% voltage variation for a 40 Deg. C change. | ±1% voltage variation for a 40 Deg. C change. |
Response time | <4 ms | <4ms |
Frequency compensation | 1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz | 1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz |
EMI suppression | Internal filter | Internal filter |
Voltage Build-Up | Internal provisions for automatic voltage build-up from generator residual voltages as low as six Vac | Internal provisions for automatic voltage build-up from generator residual voltages as low as six Vac |
Droop | 1 A or 5 A,<10 VA,adjustable from 0 to 10% at rated input current, 0.38 power factor | 1 A or 5 A,<10 VA,adjustable from 0 to 10% at rated input current, 0.38 power factor |
Operating and storage temperature | -40 Deg. C to +70 Deg.C | -40 Deg. C to +70 Deg.C |
Shock: | Withstands up to 20 g in each of three mutually perpendicular axes | Withstands up to 20 g in each of three mutually perpendicular axes |
Vibtation: | Withstands the following accelerations at the stated frequency: 0.5g; 18 to 2000Hz | Withstands the following accelerations at the stated frequency: 0.5g; 18 to 2000Hz |