Your position: > Products > Generator AVR > Caterpillar AVR >
AVC63-12B1 Generator AVR

AVC63-12B1 Generator AVR

  • publish: 2019-07-26 15:41      Browse:
  • Type:     AVC63-12B1
  • Product Summary:
  •       Description: The AVC63-12B1 Voltage Regulator is contained in an encapsulated plastic case. sensing: 220VAC ,output: 12A/65V.For 50 or 60 Hz brushless generators.The regulator includes frequency compensation with selectable slope, inverse time over-excitation shutdown, solid-state build-up circuitry, single-phase or three-phase voltage sensing, single-phase or three phase shunt, or permanent magnet power input, and parallel droop compensation, and...

Introduce
Product:
User manual:
Software Download:

Description:

The AVC63-12B1 Voltage Regulator is contained in an encapsulated plastic case. sensing: 220VAC ,output: 12A/65V.For 50 or 60 Hz brushless generators.The regulator includes frequency compensation with selectable slope, inverse time over-excitation shutdown, solid-state build-up circuitry, single-phase or three-phase voltage sensing, single-phase or three phase shunt, or permanent magnet power input, and parallel droop compensation, and an accessory input. The accessory input provides compatibility (分行点)with accessories such as a var/power factor controller.


VR6

SpecificationK65-12BK125-10B
Output power(with a 240 Vac input)12Adc @ 65 Vdc Max cfontainuous; 25 Adc @ 125 Vdc forcing for 10 seconds10 Adc @ 125 Vdc max continuous. 20 Adc @ 250 Vdc forcing for 10 seconds.
AC input power100 to 280 Vac, single-phase 50 to 400 Hz; or 63 to 105 Vac three-phase, 50 to 400 Hz; 1092 VA max continuous burden180 to 280 Vac, single-phase or three-phase, 50 to 400 Hz, 1750 VA max continous burden.
AC sensing voltage90 to 140 Vac, 50/60 Hz; single-or-three phase.90 to 140 Vac, 50/60 Hz; single-or-three phase.
External voltage adjust rheostat10K ohm, 2W, potentiometer10K ohm, 2W, potentiometer
Regulation accuracy±0.5% Average responding±0.5% Average responding
Voltage drift±1% voltage variation for a 40 Deg. C change.±1% voltage variation for a 40 Deg. C change.
Response time<4 ms<4ms
Frequency compensation1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz
EMI suppressionInternal filterInternal filter
Voltage Build-UpInternal provisions for automatic voltage build-up from generator residual voltages as low as six VacInternal provisions for automatic voltage build-up from generator residual voltages as low as six Vac
Droop1 A or 5 A,<10 VA,adjustable from 0 to 10% at rated input current, 0.38 power factor1 A or 5 A,<10 VA,adjustable from 0 to 10% at rated input current, 0.38 power factor
Operating and storage temperature-40 Deg. C to +70 Deg.C-40 Deg. C to +70 Deg.C
Shock:Withstands up to 20 g in each of three mutually perpendicular axesWithstands up to 20 g in each of three mutually perpendicular axes
Vibtation:Withstands the following accelerations at the stated frequency: 0.5g; 18 to 2000HzWithstands the following accelerations at the stated frequency: 0.5g; 18 to 2000Hz


More
Dongguan Tuancheng automation equipment Co., Ltd. all rights reserved.
Sales Phone: 86-769-23162896 Fax:86-769-23162896-609、23166296