VR6 Geneartor AVR
- publish: 2014-03-31 20:10 Browse:
- Type: VR6
- Product Summary:
VR6 AVR are contained in an encapsulated plastic case, and regulator controls the DC exciter field power of conventional, 50 OR60 HZ brushless generators. Regulation is provided by sensing the generator output voltage, converting it to a DC signal and com...
Product description:
VR6 AVR are contained in an encapsulated plastic case, and regulator controls the DC exciter field power of conventional, 50 OR
60 HZ brushless generators. Regulation is provided by sensing the generator output voltage, converting it to a DC signal and
comparing the signal to a reference voltage signal. Which is provided by sensing the generator output voltage, converting it to a
DC signal and comparing the signal to a reference voltage signal. An error signal is developed and used to control the DC field
power in order to maintain a constant generator output. The regulator includes frequency compensation with selectable slope,
inverse time over-excitation shutdown, solid-state build-up circuitry,single-phase or three-phase voltage sensing, single-phase or
threephase shunt, or permanent magnet power input, and parallel droop compensation, and an accessory input. The accessory
input provides compatibility with accessories such as a var/power factor controller.
Main features:
1. Caterpillar AVR VR6 is our new design specially for Caterpillar generator.
2. Thermal stability: Less than 0.5% per 40* amblent temperature change
3. AC input power:100 to 280 VA, single-phase 50 to 400 Hz, or 63 to 105 VA; three phase , 50 to 400 Hz, 1092 VA
maximum continuous burden AC sensing voltage: 90 to 140 VA, 50/60 Hz; single- or three-phase.
4. Regulator response: Less than 4 milliseconds
Ref: AVC 63-12 AVC 125-10
Specifications:
Specification | K65-12B | K125-10B |
Output power(with a 240 Vac input) | 12Adc @ 65 Vdc Max cfontainuous; 25 Adc @ 125 Vdc forcing for 10 seconds | 10 Adc @ 125 Vdc max continuous. 20 Adc @ 250 Vdc forcing for 10 seconds. |
AC input power | 100 to 280 Vac, single-phase 50 to 400 Hz; or 63 to 105 Vac three-phase, 50 to 400 Hz; 1092 VA max continuous burden | 180 to 280 Vac, single-phase or three-phase, 50 to 400 Hz, 1750 VA max continous burden. |
AC sensing voltage | 90 to 140 Vac, 50/60 Hz; single-or-three phase. | 90 to 140 Vac, 50/60 Hz; single-or-three phase. |
External voltage adjust rheostat | 10K ohm, 2W, potentiometer | 10K ohm, 2W, potentiometer |
Regulation accuracy | ±0.5% Average responding | ±0.5% Average responding |
Voltage drift | ±1% voltage variation for a 40 Deg. C change. | ±1% voltage variation for a 40 Deg. C change. |
Response time | <4 ms | <4ms |
Frequency compensation | 1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz | 1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz |
EMI suppression | Internal filter | Internal filter |
Voltage Build-Up | Internal provisions for automatic voltage build-up from generator residual voltages as low as six Vac | Internal provisions for automatic voltage build-up from generator residual voltages as low as six Vac |
Droop | 1 A or 5 A, <10 VA,adjustable from 0 to 10% at rated input current, 0.38 power factor | 1 A or 5 A, <10 VA,adjustable from 0 to 10% at rated input current, 0.38 power factor |
Operating and storage temperature | -40 Deg. C to +70 Deg.C | -40 Deg. C to +70 Deg.C |
Shock: | Withstands up to 20 g in each of three mutually perpendicular axes | Withstands up to 20 g in each of three mutually perpendicular axes |
Vibtation: | Withstands the following accelerations at the stated frequency: 0.5g; 18 to 2000Hz | Withstands the following accelerations at the stated frequency: 0.5g; 18 to 2000Hz |