ESD5520 Genset governor
- publish: 2019-07-30 18:21 Browse:
- Type: ESD5520
- Product Summary:
Description TESC5520E Speed Governor is specially designed for Cummins EFC series executor with the same function as ESC5500E. It has added start-up fuel volume control and smooth slow start process control. These new features can solve the black smoke phenomenon caused by rapid refueling during the start-up process of the engine, greatly improving the engine life.It is rugged enough to be placed in a control cabinet or engine mounted encosure wit...
Description
TESC5520E Speed Governor is specially designed for Cummins EFC series executor with the same function as ESC5500E. It has added start-up fuel volume control and smooth slow start process control. These new features can solve the black smoke phenomenon caused by rapid refueling during the start-up process of the engine, greatly improving the engine life.It is rugged enough to be placed in a control cabinet or engine mounted encosure with other dedicated control equipment.
(5520E is designed for EFC series.)
Isochronous Operation/Steady Stability---- +/-0.25% or better
Supply----12 or 24 VDC Battery Systems(transient&reverse voltage protected)
Power Consumption----50 ma continuous plus acutator current
Maximum Actuator Current at 25celsius (77celsius F)----10 Amps continuous
Specification
Input | Supply | 12 or 24 VDC Battery System (Transient and Reverse Voltage) |
Polarity | Negative Ground (Case Isolated) | |
Power Consumption | 50 ma continuous plus actuator current | |
Actuator Current Range @ 25 Deg. C - (Inductive Load) | Min.2.5 Amps; Max. 10Amps continuous | |
PID | PID parameter is different with ESD5500 | |
Speed Sensor Signal | 0.5-120 Volts RMS | |
Performance | Isochronous Operation/Steady State Stability | ±0.25% or better |
Speed Range/Governor | 1K to 7.5K Hz continuous | |
Speed Drift with Temperature | ±1 Max | |
Idle Adjust CW | 60% of set speed | |
Idle Adjust CCW | Less than 1200 Hz. | |
Droop Range | 1-5% regulation | |
Droop Adj. Max. (K-L Jumpered) | 400 Hz., ±75Hz. Per 1.0A change | |
Droop Adj. Min. (K-L Jumpered) | 15Hz., ±6Hz. Per 1.0A change | |
Speed Trim Range | ±200 Hz | |
Remote Variable Speed Range | 500 - 7.5 Hz. Or any part there of | |
Terminal Sensitivity J | 100 Hz., ± 15Hz / Volt @ 5.0 K Impedance | |
Terminal Sensitivity L | 735 Hz., ±60 Hz / Volt @ 65 K Impedance | |
Terminal Sensitivity N | 148 Hz., ±10 Hz / Volt @ 1 Meg. Impedance | |
Terminal Sensitivity P | 10 VDC Supply @ 20 ma Max | |
Environmental | Ambient Operating Temperature Range | -40 to +85 Deg. C |
Relative Humidity | Up to 95% | |
All Surface Finishes | Fungus Proof and Corrosion Resitant | |
Reliability | Vibration | 1G at 20 to 100 Hz. |
Testing | 100% Functionally Tested |