PX350 Generator AVR
- publish: 2021-01-15 16:49 Browse:
- Type: PX350
- Product Summary:
SPECIFICATION: Power Sensing Input: Voltage: 85 ~ 135 VAC / 190 ~ 240 VAC Frequency: 50 / 60 Hz, Jumper selectable Output: Voltage: Max. 36 VDC @ 120 VAC input Max. 73 VDC @ 240 VAC input Current: Continuous 4A Intermittent 7A for 10 sec (52 / 105VDC) Resistance: Min. 15 ohm Max. 100 ohm Voltage Regulation: ± 1% ( with 4% engine governing ) Voltage Build-up: Residual voltage at AVR terminal 5 VAC Operating Temperature: - 40°C ~ 60°C Storage Tem...
Description
AVR PX350 is an encapsulated electronic voltage regulator (分行点)that controls the output of a brushless AC generator (分行点)by regulating the current into the exciter field.Input power and sensing is achieved through terminals 3 and 4. The voltage input requirement of the PX350 is 120 to 240 VAC.The screwdriver adjustable potentiometer adjusts the generator output voltage. Adjustment clockwise increases the generator output voltage.Power & Sensing Input,Voltage 85~135VAC/190~240VAC,Frequency 50/60 Hz,Jumper selectable.
Voltage Buil-up:Residual voltage at AVR terminal >5 VAC.
SPECIFICATION:
Power & Sensing Input:
Voltage: 85 ~ 135 VAC / 190 ~ 240 VAC
Frequency: 50 / 60 Hz, Jumper selectable
Output:
Voltage: Max. 36 VDC @ 120 VAC input Max. 73 VDC @ 240 VAC input
Current:Continuous 4A Intermittent 7A for 10 sec (52 / 105VDC)
Resistance:Min. 15 ohm Max. 100 ohm
Voltage Regulation: < ± 1% ( with 4% engine governing )
Voltage Build-up:Residual voltage at AVR terminal > 5 VAC
Operating Temperature: - 40°C ~ 60°C
Storage Temperature: - 65°C ~ 85°C
Burden: 250 / 500VA Max.
External Volts Adjustment: ± 5% with 1K ohm 1 watt trimmer ± 10% with 2K ohm 1 watt trimmer
EMI Suppression: Internal electromagnetic interference filtering
Unit Power Dissipation:
Max. 8 watt
Under Frequency Protection (Factory Setting)
60 Hz system presets knee point at 54 ~ 61 Hz
50 Hz system presets knee point at 45 ~ 51 Hz
Dimensions:148mm L * 80mm W * 47.5mm H
Weight: 262g ± 2%
Certification: EN61204-3 : 2001 certified Test Report on request if required