K65-12B Voltage Regulators
- publish: 2014-01-01 17:03 Browse:
- Type: K65-12B
- Product Summary:
The K65-12B and K125-l0B Voltage Regulators are contained in an encapsulated plastic case. The regulator controls the DC exciter field power of conventional, 50 or 60 Hz brusliless generators. Regulation is provided by sensing the generator output voltage,converting it to a DC signal and comparing the signal to a reference voltage signal. ...
Product description:
The K65-12B and K125-l0B Voltage Regulators are contained in an encapsulated plastic case. The regulator controls the DC exciter field power of conventional, 50 or 60 Hz brusliless
generators.Regulation is provided by sensing the generator output voltage,converting it to a DC signal and comparing the signal to a reference voltage signal. An error signal is developed
and used to control the DC field power in order to maintain a constant generator output.The regulator includes frequency compensation with selectable slope,inverse time over-excitation
shutdown, solid-state build-up circuitry,single-phase or three-phase voltage sensing, single-phase or three-phase slnint, or permanent magnet power input, and parallel droop
compensation, and an accessory input. The accessory input provides compatibility with accessories such as a var/power factor controller.
Specifications:
Output power (with a 240Vac Input):12 Adc @ 65 Vdc maximum continuous.25 Adc @ 125 Vdc forcing for 10seconds.
AC input power: 100 to 280 Vac, single-phase 50to 400 Hz, or 63 to 105 Vac;
threephase,50 to 400 Hz, 1092 VA maximum continuous burden
AC sensing voltage: 90 to 140 Vac, 50/60 Hz; single- or three-phase.
External voltage adjust rheostat: 10k ohm, 2 W, potentiometer
Regulation accuracy: ±0.5% Average responding
Voltage drift: ±1% voltage variation for a 40° C(104° F) change.
Response time: < 4 milliseconds
Frequency compensation: 1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65Hz
.
EMI suppression: Internal filter
Voltage Build-Up: Internal provisions for automatic voltage build-up from generator residual voltages as low as six Vac.
Overexcitation shutdown: Overexcitation protection starts timing at 90 Vdc ±5% and takes the output to zero in greater than 30 seconds.
The output can be 125Vdc for greater than 10 seconds.
Droop: 1 A or 5 A,<10 VA, adjustable from 0 to 10% at rated input current, 0.8 power factory
UL recognized/CSA certified: UL Recognized per Standard 508,UL File NO. E97035. CSA certified per
Standard CAN/CSA-C22.2 No.14-95, CSA File No. LR 23131