LXC7X10 series generator controller wiring diagram and common faults and elimination method
LXC7X10 series generator controller application wiring diagram
2. Common failures and troubleshooting methods
Here are more common in the process of using my company controller failure and its elimination method, if other can't solve problems, please do not hesitate to contact our company.
The fault phenomenon | May take measures |
Controller, electric | Check the starter battery Check the terminal controller Check the dc insurance |
Generator outage | Check below the main interface of warning Check the ac generator voltage Check the dc insurance |
The controller emergency stop | Check the stop button and function is correct Check the starter battery anode is properly connected to the emergency stop losing Check the attachment whether there is open circuit |
Low oil pressure alarm after a successful start | Check the oil pressure sensor and its attachment |
After the success of the starting temperature/cylinder high temperature alarm | Check the temperature sensor and its attachment |
Running in the alarm stop | According to check the LCD display information related to switch and the attachment Check the programmable input port |
Starting is not successful | Check fuel circuit and its connections Check the starter battery Check the speed sensor and its cable Check the engine manual |
Starter have no reaction | Check the starter cable Check the starter battery |
But not ATS switch unit operations | Check the ATS Check the connecting cables between controller and ATS |
RS485 communication properly | Check the attachment Check the COM port Settings are correct. Check whether A and B line of RS485 is reverse Check whether RS485 converter module damage Check the PC communication port is damaged |