Could you tell me LXC701 generator controller connection
Since the launch of LXC701 generator controller is a controller, high reliability, simple installation, convenient operation, high cost performance, is a more popular controller, we mainly introduce below, LXC701 controllerWiring, mainly is 14 terminals, specific as follows:
Terminal 1 (B) : external starting battery cathode.
Terminal 2 (B +) : external starting battery positive electrode.
Terminal 3 (Em. Stop input) : emergency stop input (input B + voltage effective), an external emergency stop normal close button.
Mixer terminal 4 (arg, the Output) : Fuel outlet (B +), an external Fuel relay, contact capacity 5 a.
Terminal 5 (Start Output) : starting outlet (B +), external starter relay, contact capacity 5 a.
Terminal 6 (Remote Start Input) : Remote boot Input port, B - effectively.
Terminal 7 (D +) : after charging generator WL (or D +) terminal, internal provide charger controller excitation current.When charging charging generator failure (i.e., in the process of running D + terminal voltage is less than the default value), long charging failure indicator light on the front panel (charging failed non-stop, indicating only).
Terminal 8 configured (LOP) : low oil pressure switch signal Input port, B - effectively.
Terminal 9 (HWT) Input) : high temperature/cylinder temperature switch Input port, and the B - effectively.
Mixer terminal 10 (Configurable Output3) : (B +), programmable output contact capacity 5 a.Switch output can be set up by a computer.
11 pieces terminals (Configurable Output2) : (B +), programmable output contact capacity 5 a.
12 pieces terminals (Configurable Output1) : (B +), programmable output contact capacity 5 a.
Mixer terminal 13 (N), 14 (L) : external generator voltage signal, judge success and provides overspeed starting/low speed protection.
USB interface: used in the controller parameter programming through the USB cable to connect the computer directly.