After the generator controller wiring high temperature alar
1 After the generator controller wiring high temperature alarm is powered down (160 degrees)?
Q: Do you pick is connected right
Customer: Yes
Q: Are you on the 11th line received a high temperature alarm switch
Customer: Yes
Q: Are you on the 12th line received a low oil pressure alarm switch
Customer: Yes
Q: Your cable is connected to 44 oil pressure sensor
Customer: Yes
Q: Are you the No. 45 line received a temperature sensor
Customer: Yes
Q: Are you the No. 47 pick of the battery ground cable
Customer: Yes
No reason ah, it should be right ah. Wonder ah, I thought, customers will also pick up other lines
Your line is the high water temperature and low oil pressure alarm alarm reversed, see if you can turn to take over.
Customer: Yes, I reversed the line, everything is normal, thank you very much.