Generator set start after normal high voltage (600 v three-p
Generators normally appears after starting high voltage (three-phase 600V) voltage of about 10 seconds there is no how to do?
Q: Do you pick is connected right?
Customer A: Yes
Q: Your VII line is zero line generators
Customer A: Yes
Q: Your six / Floor line is connected to generators L1 and L2 online
Customer A: Yes
Engineer: Then you adjust the potentiometer counterclockwise RMS tune a little bit like a
Customer: RMS potentiometer good tune, but the voltage (320V) about ten seconds of no voltage.
Engineer: That you: tune OVER V potentiometer (clockwise adjustment)
Customer: tune OVER V potentiometer Well, appears high voltage (three-phase 410V) can not be reduced, may increase.
Engineer:Your unit has adjustable resistance do just fine if you do not have to install a