Q:Generator stator in the operation of three-phase current unbalance What are the reasons? How to deal with?
A: The main reasons are:
1, generator internal faults such as: Stator Windings, winding break;
2, the system load Unbalanced: If the system has a single phase electric stove, electric locomotives and other asymmetric load;
3, the system failure occurred asymmetry protection tripping;
4, the main generator breaker phase running.
Treatment:
One asks whether due to scheduling system caused the system caused by the case, you should adjust the generator active and reactive load, the difference of the three-phase current imbalance controlled within 8% Ie, and shall not exceed the rated maximum phase.
2, treatment of non-full-phase generator main circuit breaker failure.
3, if not a system malfunction and cause the main circuit breaker, deal with generators, transformers and other comprehensive qualifying examination, if necessary, power outage inspection.
4, in the three-phase current imbalance is running, should closely monitor the generator rotor temperature must not exceed the permissible value.