1、 Specifications
Detection and power input
Voltage 190 ~ 264Vac single phase two wire
The frequency is 50 / 60Hz to be set by bridging copper
Output
Maximum 90vdc at 207vac input
The current is 4A continuous and 10A discontinuous in 10 seconds
Minimum resistance 15 Ω
Voltage regulation rate
< ± 1% (when engine change < 4%)
Temperature difference stability
The voltage drift is 0.05% per ℃ change
External voltage adjustment
Use 1K Ω Watt potentiometer ± 8%
The voltage builds up slowly for 2 seconds
Droop input
The highest sensitivity of 0.07a corresponds to 5% pressure drop (when pf = 0)
Maximum input 0.33A
Voltage build up
The remanence voltage of AVR input terminal should be more than 5VAC
Power consumption
Maximum 12watt
Low frequency protection
Factory set point: at 95% Hz
Slope: 170% at 30Hz
Voltage correction
Maximum input: ± 5 VDC
(analog input)
sensitivity: 5% generator voltage can be adjusted every 1vdc
Input resistance: 1K Ω
Current compensation
Load: 10 Ω
size
150mmL*135mmW*40mmH
Weight
418 G ± 2%